Please read the table below to ensure suitability for your application prior to purchase as the software is not returnable due to this cause.


  Single-Phase Three-Phase Direct Current
 Parameter  Minimum Input  Maximum Input Minimum Input Maximum Input Minimum Input Maximum Input
 Accepted  Accepted  Accepted  Accepted  Accepted  Accepted
           
Current (kA) 0.2 100 0.2 80 0.2 80
Duration (cycles of 60 Hz current) 0.05 1000 0.05 1000 0.05 1000
Arc Gap (in.) 1 72”, but status indicates beyond range of verification test data (20”) 1 50”, but status indicates beyond range of verification test data (24”) 1 36”, but status indicates beyond range of verification test data (20”)
Distance to Arc (in.) 0.4 400 0.4 400 0.4 400
Source Voltage (V) No lower limit 500,000 No lower limit 120,000 No lower limit 1,200
Electrode Material Stainless steel 
 Copper


Monday, October 29, 2018

« Back